GENLINK DPNL is a multiple winding reactor and when installed in the common neutral of paralleled sources either between the dissimilar generators or the generator and the Utility supply it can greatly reduce the neutral circulating currents that result from the instantaneous voltage differences. These neutral circulating currents, which are predominantly triple frequency, have the potential to cause a considerable amount of damage with respect to overheating generators and causing false-protection trips.

Voltage differences in paralleled generators made by different manufacturers or differences in standard pitch design configurations in generators made by the same manufacturer can result in heavy neutral circulating currents. Additionally, alternative energy sources such as solar and wind power that generates AC power can introduce heavy circulating currents in 4-wire parallel applications. GENLINK when applied, will impede the flow of circulating currents while adding only minimal impedance to the fault current path.

GENLINK DPNL can be used in both 3-wire and 4-wire systems. For 4-wire applications where there is return neutral current from 1-Ph loads, the DPNL must be sized for this current as well as the circulating current. For 3-wire applications where there is no return neutral current from 1-Ph loads, a smaller size DPNL can be used. Grounding of the neutral must be done at only one location which is recommended to be the distribution switchboard.

nsoem001014.jpg nsoem001008.jpg nsoem001006.jpg nsoem001004.jpg
33427 Mayer Rd
Waller, TX 77484
Phone: (877) 898-5103
nsoem001003.jpg
Home
About Us
Solutions
Contact Us
Technical
Discussions
Project
Experience
NSOEM
Renewal Parts Operation
NSOEM
ES&D
Operation
Client Links
About Us
Transformer Solutions
Harmonic Modeling Services
ES&D Services
Harmonic Solutions